Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.39 - Low Oil Protection | 3.26.9 Low Oil Protection (Re-Inspection) | This unit reverts back to Auto operation after low oil timer trips, without requiring a physical reset. | 3/21/2023 | ||
A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | % year rupture valve test is due. Last performed in 2016. |