Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x mergency power must be tested. Re-inspection required 12/17/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.27 x Need to perform the required Cat 1 emergency generator testing to complete the annual testing. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 8.11.2.1.1(b) (Re-Inspection) In car stop switch shall be overridden when car is in flight on Phase 1 Fire Service. Reinspection Required. 7/16/2020
conversion conversion n/a Test cab two way communitcation 7/16/2020
conversion conversion n/a Test recall from fire command center switch 7/16/2020
conversion conversion n/a Relocate all elevator lobby smoke detectors further that 2 ft from car door 7/16/2020
conversion conversion n/a Extend pit ladder to the required 48 inch height above access sill 7/16/2020
conversion conversion n/a Reduce counterweight runby to the pit posted demension 7/16/2020
conversion conversion n/a Plug all hoistway to machine room penetrations 7/16/2020
conversion conversion n/a Hoistway access switches inoperative 7/16/2020
conversion conversion conversion - reinspect x Install all corridor call station pictographs. 7/23/2018
conversion conversion n/a Mark floor numbers on corresponding hoistway doors, car side 7/16/2020
conversion conversion n/a Install all hoistway duct covers including any for car top 7/16/2020
conversion conversion n/a Install 2nd pit stop switch 47 in from pit floor 7/16/2020