conversion conversion n/a No No Extend pit ladder to the required 48 inch height above access sill 7/16/2020
conversion conversion n/a No No Hoistway access switches inoperative 7/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 8.11.2.1.1(b) (Re-Inspection) No No In car stop switch shall be overridden when car is in flight on Phase 1 Fire Service. Reinspection Required. 7/16/2020
conversion conversion n/a No No Install 2nd pit stop switch 47 in from pit floor 7/16/2020
conversion conversion conversion - reinspect Yes No Install all corridor call station pictographs. 7/23/2018
conversion conversion n/a No No Install all hoistway duct covers including any for car top 7/16/2020
conversion conversion n/a No No Mark floor numbers on corresponding hoistway doors, car side 7/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 Yes No mergency power must be tested. Re-inspection required 12/17/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 3.27 Yes No Need to perform the required Cat 1 emergency generator testing to complete the annual testing. Re-inspection required 7/30/2025
conversion conversion n/a No No Plug all hoistway to machine room penetrations 7/16/2020
conversion conversion n/a No No Reduce counterweight runby to the pit posted demension 7/16/2020
conversion conversion n/a No No Relocate all elevator lobby smoke detectors further that 2 ft from car door 7/16/2020
conversion conversion n/a No No Test cab two way communitcation 7/16/2020
conversion conversion n/a No No Test recall from fire command center switch 7/16/2020