MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x This inspection did not get completed. Need to perform testing on the following items: buffer testing, emergency lighting, door pressure, emergency phone & fire service. Re-inspection required 8/8/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Remove all drywall screws penetrating front wall of hoistway. All lands. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Provide all hoistway door bottom retainer guides, all floors. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on the main line disconnect, in the elevator machine room. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on the 110v. disconnect, in the elevator machine room. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.3.2 Pit light switch is not accessible from the pit access door an additional stop switch is required stop switch is not overidden on fire service 8/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 8.6.4.11 x x This elevator has excessive amount of runby, the C measurement is 14.5 and cannot get to the buffers. The hoist ropes were altered / replaced without a permit or inspection. Red-tagged, Re-inspection required 8/8/2024