MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
This inspection did not get completed. Need to perform testing on the following items: buffer testing, emergency lighting, door pressure, emergency phone & fire service. Re-inspection required
|
8/8/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
|
|
Remove all drywall screws penetrating front wall of hoistway. All lands.
|
4/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
2.11
|
|
|
Provide all hoistway door bottom retainer guides, all floors.
|
4/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
Provide feeder location on the main line disconnect, in the elevator machine room.
|
4/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
Provide feeder location on the 110v. disconnect, in the elevator machine room.
|
4/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.3.2
|
|
|
Pit light switch is not accessible from the pit access door an additional stop switch is required stop switch is not overidden on fire service
|
8/12/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.6.4.11
|
x
|
x
|
This elevator has excessive amount of runby, the C measurement is 14.5 and cannot get to the buffers. The hoist ropes were altered / replaced without a permit or inspection. Red-tagged, Re-inspection required
|
8/8/2024
|