Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - n/a n/a The pit light swith is not accessible from the pit access door 8/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Provide all hoistway door bottom retainer guides, all floors. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Remove all drywall screws penetrating front wall of the hoistway, all lands. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on the main line disconnect in the elevator machine room. 4/5/0202
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on the 110v. disconnect in the elevator machine room. 4/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x 2.27.3.1.1-On the primary recall floor for fireman’s service, the phase I key switch failed to initiate fireman recall as required. The key switch shall be repaired/replaced and a reinspection performed within 10 days or the elevator shall be removed from service and a red tag issued (note that all other initiating recall devices operate as required). 6/13/2025