Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 In case of fire don't use elevator signage needed 4/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Telephone Incoming line is inactive new provider missed Elevator phone Requirement. 5/4/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency telephone didn't have an active signal. Alarm Bell worked. Must reinspect when violation is corrected. Low usage building. 4/19/2024
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door needs to be self-closing and self-locking 4/25/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) MCP needed 4/25/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Machine room needs fire extinguisher 4/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 x Complete fire caulking in hoistway, and seal any/all penetrations. 4/9/2018