ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.12 - Car enclosure
|
2.14
|
|
|
Need to install top of car railing. There is more than a 12 inch clearance from car enclosure to hoistway wall. Fall hazard is present.
|
7/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Provide documentation of monthly firefighter operation. Documentation needs to be viewable on site.
|
7/16/2021
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.20.10
|
x
|
x
|
Braking system does not safely stop and hold the elevator car.
|
6/17/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
Need to test firefighter operation
|
9/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.11.2.1.5(j)
|
x
|
|
Perform annual no load safety test
|
9/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate. Phone line issue
|
5/31/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
PHONE NOT WORKING HAS DIAL TONE BUT NOT CALLING OUT
|
5/31/2024
|