Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Pit light switch shall be accessible from the pit access door. 11/21/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits 2.2.5.3 - The pit light switch shall be accessible from the pit access door. 1/25/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 11/21/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(k) The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10 Emegency Operation and Signaling Devices x The seismic displacement switch shall be operational. 12/14/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation The MCP is not being filled out. The MCP shall specify examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. 10/6/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 11/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 x Fire gibs are missing from hoistway doors. 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.14 - Code data plate 8.9 Install a code data plate. It shall read A17.1-2004. 11/9/2021