Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x Phone, emergency bell and emergency light failed to operate. Elevator was red tagged power shut off at disconnect. Email sent to office. 12/19/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light shall work. 5/13/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light failed to operate during test. 3/1/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency lighting shall work. 5/13/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm shall work. 3/20/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Only items relating to the operation of the elevator shall be stored in the machine room. All non-elevator related materials shall be removed from the machine room. 5/13/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A ABC type fire extinguisher shall be provided in the machine room. 5/13/2019
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 1001.2(c)(18) All hoistway wiring shall be enclosed in conduit. 5/13/2019
A17.1-1996 : Elevators 3.14 - Hoistway clearances 1001.2(c)(20) x Complete fascia is required to maintain proper car clearances. 7/9/2019
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) The distance between the inside face of the hoistway door and the edge of the landing sill shall be less than 3". 5/13/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits A pit light switch is required. 5/13/2019
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)10 x A Category 5 full load test shall be witnessed. 3/20/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - "Do not use in case of fire" signage is required. 5/13/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A variance shall be requested to allow a residential elevator to be installed in a commercial application. 5/13/2019