ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.26 - Secondary and deflector sheaves
|
8.11.2.1.2(x)
|
|
x
|
Anchor points on primary deflector sheave, in pit, severley corroded and questionable.
|
9/5/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.16 -Overhead Beam and Fastenings
|
8.11.2.1.2(n)
|
|
|
Isolation grommets on bedplate detiorated, in need of replacement.
|
12/20/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
6/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Provide guarded, overhead lighting in machine room.
|
12/20/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Provide pit switch in pit.
|
12/20/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
Provide self closing/locking mechanism on machine room door.
|
12/20/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Provide type ABC fire extinguisher in machine room.
|
12/20/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
x
|
Suspension ropes cross winding on drum, damaging cables.
|
9/5/2019
|