Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on emergency power shall be tested operating on emergency power annually.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in-car telephone shall be operational. 6/7/2024
conversion conversion n/a No No Machine space lighting needs to be 19fcs to work inhoistway machine room for space. 7/26/2018
conversion conversion n/a No No Needs to be 19fcs in pit to work on equipment. 7/26/2018
conversion conversion n/a No No Fire extinguisher on carptop for machine space. 7/26/2018