Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all non elevator related items from the elevator machine room. 6/3/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide existing battery backup lowering unit to work properly. 8/1/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) Yes No Emergency battery lowering device was removed. Need to re-install it, it is a safety device. Re-inspection required
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Battery backup lowering unit not working correctly. 4/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Provide existing emergency lights and bell to work properly. 8/1/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Need to install protective guards around bulbs to contain broken glass. 5/1/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13 Door Systems Yes No All hoistway doors require two bottom door guides and one fire retainer.(minimum) 4/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers No No Replace sump cover. 8/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures No No Post Phase I instructions. 8/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph No No Need to install "Do not use elevator in case of fire" sign 5/1/2024