MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
G(1)/8.6.4.15/1.5.1(b) : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED)
|
1/19/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
G(1)/8.6.4.15/1.5.1(b) : Emergency/auxiliary lighting shall work with power loss. (REINSPECTION REQUIRED)
|
1/19/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair rear handrail inside cab
|
1/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair COP side reveal panel (damaged, exposing bulbs and wiring)
|
3/15/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking. Push button locking not allowed, and closer does not fully close door.
|
3/15/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine lighting must be protected
|
12/4/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
H(5) Machine room lighting needs to be guarded
|
3/15/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room light must be guarded
|
6/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide mcp in machine room
|
6/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.6 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized)
|
3/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
MCP shall be kept in equipment room, including Oil loss log and Fire service testing log, recorded monthly.
|
1/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired)
|
1/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace missing hall fire signage “ in case of fire…..”
|
3/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
11 CSR 40-5.070 : ADA Requirements: buttons missing Braille Identification.
|
3/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
clean cartop and pit, excessive debris
|
1/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
G/8.6.5.5.2 Pit scavenger pump will be removed or routed to a measurable container.
|
1/21/2022
|