ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Repair Machine Room Heat/Smoke detector that is hanging by it's wiring from ceiling.
|
8/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
|
|
Provide oil collection bucket in pit
|
7/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
1/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 7/20)
|
1/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag.
|
8/1/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
|
1/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS)
|
1/22/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS)
|
1/22/2021
|