Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall give proper location message, ( no Location message given). 5/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x 6.4.2(b)(3): In Car Stop Switch shall be inoperable while in flight, while on Phase 1 return.(2000 and later) 5/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x 6.4.2(b)(3): In Car Stop Switch shall be inoperable while in flight, while on Phase 1 return.(2000 and later) 5/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall give proper location message, ( no Location message given). 5/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. 6/3/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. 6/3/2022