ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall give proper location message, ( no Location message given).
|
5/5/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall give proper location message, ( no Location message given).
|
5/5/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
6.4.2(b)(3): In Car Stop Switch shall be inoperable while in flight, while on Phase 1 return.(2000 and later)
|
5/5/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
6.4.2(b)(3): In Car Stop Switch shall be inoperable while in flight, while on Phase 1 return.(2000 and later)
|
5/5/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly.
|
6/3/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room.
|
6/3/2022
|