Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 No No Permanent electric lighting shall be provided in all machine rooms. Illumination shall not be less than 200 1x (19fc) at floor. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 No No Provide lighting of at least 19 fc at floor of control spaces, including hoistways 4/6/2026
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV is not sealed. Perform test within 90 days, tag and seal upon completion. 10/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 8/2/2023