Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed 11/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed 11/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed 12/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed 12/23/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Owner shall apply for a variance to keep residential elevator in a public location. 1/21/2021
MO Minimum : Elevators (I) - Pits (I)7 Pit needs stop switch 11/8/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room shall be fully enclosed. A ceiling shall be installed to complete enclosure. 1/21/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light and bell not working. Phone works. 11/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light and bell not working. Battery 10/5/2023
MO Minimum : Elevators (F) - Electrical Switches (F)9 Machine room electrical disconnect shall be fused and lockable. 1/21/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 The clearance between the hoistway doors or gates and the hoistway edge of the landing sill shall not exceed 3 inches. The distance between the hoistway face of the landing door or gate and the car door or gate shall not exceed 5 inches. 1/21/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 Sill to sill running clearance shall not exceed 1.5 inches. 1/21/2021