Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/1/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/28/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting More light is needed at the 6th floor landing. The controller is located on this level in the jamb.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A written maintenance control program shall be kept on site for each elevator. It shall include on site documentation of all applicable items listed in section 8.6.1.2.2. 8/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Top of car needs to be cleaned.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit needs to be cleaned.