Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) There is no fire extinguisher in access of the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 7/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) An electrical wiring duct cover is missing in the elevator hoistway. Replace and reinstall the missing cover. 7/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits The elevator pit floor is covered in hydraulic oil and shall be kept clean and dry. 7/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Elevator pit is covered in hydraulic oil, it shall be kept clean and dry. 8/12/2021