ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The elevator pit floor is covered in hydraulic oil and shall be kept clean and dry.
|
7/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Elevator pit is covered in hydraulic oil, it shall be kept clean and dry.
|
8/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
There is no fire extinguisher in access of the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
7/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.2.1.3(r)
|
|
|
An electrical wiring duct cover is missing in the elevator hoistway. Replace and reinstall the missing cover.
|
7/19/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
8.11.3.1.2 (o)
|
x
|
|
Hydraulic control valve is leaking fluid back into tank, needs repaired. Re-inspection required
|
3/16/2023
|