Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevators equipped with emergency power shall be tested annually. Reinspection required for emergency generator power 6/9/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone could not provide 2-way communication, needs repaired. Re-inspection required 8/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator has emergency generator back-up power, which needs to be scheduled, tested and witnessed by an inspector. Re-inspection required 8/25/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No There is no fire extinguisher in access of the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 8/12/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No The elevator pit floor is covered in hydraulic oil and shall be kept clean and dry. 8/12/2021