ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators equipped with emergency power shall be tested annually. Reinspection required for emergency generator power
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The elevator pit floor is covered in hydraulic oil and shall be kept clean and dry.
|
8/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
There is no fire extinguisher in access of the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
8/12/2021
|