Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 5/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Phase I fire service key switch is missing the bezel with "reset, off and on" wording, need to replace fire service bezel. Re-inspection required 5/7/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed or tagged. Perform OSV test on or before next annual inspection. 4/12/2022