ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed or tagged. Perform OSV test on or before next annual inspection.
|
4/12/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required
|
5/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Phase I fire service key switch is missing the bezel with "reset, off and on" wording, need to replace fire service bezel. Re-inspection required
|
5/7/2024
|