Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11 x Emergency phone shall work.
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.3 x 1) The lift shall be provided with a means of twoway conversation between the platform and a readily accessible point outside the runway which is available to emergency personnel. 11/2/2020
ASME A18.1-2005 : Lifts & Chairlifts 2.6 - Platforms 2.6.6.2 2) During operation, the minimum illumination on the floor and controls shall be not less than 5 fc. 5/12/2022
ASME A18.1-2005 : Lifts & Chairlifts 2.8 - Safeties and Speed Governors 2.8 x A category 5 test shall be performed. Unit is overdue for a category 5 test. 5/6/2025