Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) Provide a current tested fire extinguisher in the elevator machine room. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide feeder location on main line and 110v disconnect. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display a copy of the current state operating certificate. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.11.2.1.1(o) Post elevator lobby warning placards on all floors. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Provide elevator numbering inside hoistway at all doors. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a completed maintenance control program (MCP) on site. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Provide floor numbering on inside of hoistway doors. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Provide "In case of fire" signage on all floors. 12/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Hoistways shall have floor numbers, not less than 4 inches in height, on the hoistway side of the hoistway door.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.2.1.3(w) Stops shall be provided to prevent hoistway door hangers from overrunning the track.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.9 - Power closing of doors or gates 8.11.2.1.1(i) The door data plate shall be completed with the door speeds.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.4 - Sills and car floor 8.11.2.1.1(d) There is missing carpet inside the car that creates an unlevel and unsafe surface.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) The position indicator shall be securely attached to the car enclosure.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the machine room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency two-way communication does not work when car 110v removed. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency recording gives the wrong location. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.4 - Normal terminal stopping devices 8.11.2.2.5 x The bottom limit switch shall be adjusted to stop the movement of the car prior to striking the buffer. 4/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 8.11.2.1.3(g) x The upper terminal device shall be adjusted to stop the movement of the car prior to contacting the directional limit switch. 4/25/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.4 - Normal terminal stopping devices 8.11.2.2.5 x The bottom limit switch shall be adjusted to stop the movement of the car prior to striking the buffer. 3/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 8.11.2.1.3(g) x The upper terminal device shall be adjusted to stop the movement of the car prior to contacting the directional limit switch. 3/2/2022