Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 replace entrance jamb braille at landing numbered 6. 5/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone did not connect to answering service 5/9/2024
A17.1-2016 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x Adjust the door closing force so that it is less than 30 lbs. 6/14/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) monthly fire service test log is from 2021, need 2022 log and deeds to be done monthly 10/5/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 5/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.16 - Traveling cables and junction boxes 2.8.1 Replace the travelling cable that has a damaged jacket with exposed conductors 5/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 2.8.1 replace the traveling cable, there is a hole worn through the jacket with exposed wires some are broken 5/3/2022
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the state operating certificate is to be posted in the machine room 5/3/2022