A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the state operating certificate is to be posted in the machine room
|
5/3/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
|
5/3/2022
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
Adjust the door closing force so that it is less than 30 lbs.
|
6/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not connect to answering service
|
5/9/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
monthly fire service test log is from 2021, need 2022 log and deeds to be done monthly
|
10/5/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
replace entrance jamb braille at landing numbered 6.
|
5/3/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
2.8.1
|
|
|
replace the traveling cable, there is a hole worn through the jacket with exposed wires some are broken
|
5/3/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.16 - Traveling cables and junction boxes
|
2.8.1
|
|
|
Replace the travelling cable that has a damaged jacket with exposed conductors
|
5/3/2022
|