Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Need to repair emergency power indicator jewel for proper operation.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. 1/5/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.1.2(bb) x The remote governor activation device does not operate. Without this device in operation a category 5 test cannot be performed which will be required in 2022. Repair or replace the governor activation switch to operate as required. Reinspection required. 1/5/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.1.2(bb) x Governor overspeed switch & seal, remoter governor activation device does not work. Re-inspection required 9/22/2022
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.11.2.1.2(q) The emergency rescue battery in the controller has not been changed since the installation date. The Manufacture’s written procedure is for replacement every 3 years. If the battery becomes depleted the elevator will automatically stop operating. Replace the battery of this elevator before it shuts down due to battery being depleted.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.6.1.6.3 Rescue batteries do not appear to have been replaced, provide. Also mark date on batteries and entry in MCP.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 3/27/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 12/19/2024
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator emergency power selector switch. 12/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.7 Cleaning of Hoistways and Pits Clean down the hoistway.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Clean the car top.