Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Standby power operation of the elevator shall be tested. 8/10/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 1/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.1.3.3 No No Wiring for the cellular gateway is draped across control space and needs to be re-routed around the perimiter of space and properly supported.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide a code compliant MCP including onsite documents. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops No No The top of the car and the hoistway shall be cleaned. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.7 Cleaning of Hoistways and Pits No No Top of the car, hoistway, and doors shall be cleaned (excessive rope rouge). 4/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) No No Hoistway walls shall have smooth surfaces. Drywall screws shall not protrude into the hoistway. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No The pit shall be kept clean. Clean the pit. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Provide pit ladder rungs to be non-slip type. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Provide code compliant pit lighting. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept clean. Remove excess debris. 4/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) Yes No Provide code compliant minimum counterweight runby. 10/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be displayed in the elevator machine room. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be displayed in the machine room in a non-combustinble frame.