Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Counterweight runby is 2 1/2", 6" is minimum. Need to shorten hoist ropes to have at least 6" runby and re-inspect. Re-inspection required 6/11/2025
MO Minimum : Elevators (H) - Machine Rooms (H)1 x Replace missing smoke detector in the machine room. Reinspection required within 30 days 7/25/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test & document on log in machine room 3/17/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Replace missing smoke detector in the machine room and test within 30 days 5/15/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing and document on log in the machine room 6/17/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Test emergency power operations within 30 days 5/15/2024