Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post phase 1 fire service instructions near the fire service key switch in lobby. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Provide pit ladder rungs to be non-slip type. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Provide code complaint pit lighting. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops The top of the car and the hoistway shall be cleaned. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Clean the pit. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) Hoistway walls shall have smooth surfaces. Drywall screws shall not protrude into the hoistway. 2/6/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 2.11 Adjust upthrust roller bearings for proper clearance to door hanger track (9 & 10 floor). 4/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post phase 1 fire service instructions near the fire service key switch in the lobby. Note: Incorrect instructions are posted. 4/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Cartop light & GFI do not work. 4/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x The hoist ropes are rouged and nearing the minimum acceptable diameter. The hoist ropes shall be replaced. 8/10/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 3/29/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x The test was stopped due to ID 23591 being red-tagged. This elevator was originally scheduled for an annual and category 5 test. The only items completed were: The hoistway was run, but the pit was not. Door pressure was tested. All other annual and category 5 testing items still need to be witnessed. 1/18/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Standby power operation of the elevator shall be tested. 8/10/2021