MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Provide 4x4 box cover on box near machine in hoistway
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car does not work. RE-inspection required
|
11/2/2023
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
|
|
Provide cartop data plate with all required information stamped
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Repair hole in machine room ceiling around flex conduit
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Fire caulk around flex conduit going to battery backup unit in overhead
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
The equipment room shall be ventilated.
|
12/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
MCP shall include evacuation procedures
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/30/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needs to have maintenance records updated, including monthly fire service checks
|
|