Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Provide procedure for evacuation in MCP 3/17/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No MCP needs to have maintenance records updated, including monthly fire service checks 3/17/2026
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 No No Provide cartop data plate with all required information stamped 3/17/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 No No Provide 19 foot candles of lighting in elevator control room. Less than 3 foot candles is provided now at floor level
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Provide adequate lighting in front of controller (19fc at floor) 3/17/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 No No Repair hole in control room ceiling around large flex conduit 3/17/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 No No Repair hole in machine room ceiling around large flex conduit 3/17/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 No No Fire caulk around large flex conduit in overhead 3/17/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/30/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) No No The equipment room shall be ventilated. 12/18/2019