Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm in car does not work. Re-inspection required 11/21/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not work. Re-inspection required 11/21/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone in elevator cab does not work, needs repair. Re-inspection required 11/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) A heat detector device has been installed in the elevator hoistway and shall be removed. The heat detector device is designed to disconnect power to the elevator before a sprinkler head activation in a vital elevator controlled space. There is no sprinkler head to activate at the top of the hoistway. 10/9/2018
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post certificate 10/6/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide MCP 10/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance records. 10/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean pit. 10/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean pit 10/6/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is due for full load test and have tripping speed checked. Re-inspection required 11/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is due for full load test and have tripping speed checked. Re-inspection required 11/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is due for full load test and have tripping speed checked. Re-inspection required 4/3/2024