Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Clean debris form elevator pit 10/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Clean dirt from elevator car top 10/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 8/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Call cancel push button shall work. Did NOT red tag. Reinspect only. 8/28/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Incomplete annual inspection. Perform fire service testing. 3/31/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10 Emegency Operation and Signaling Devices x Perform uncontrolled motion test. 3/31/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on emergency power or normal power. Repair or replace 10/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x Governor remote trip / reset inoperable, needs repaired. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Check governor rope pull out and pull through force. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Check governor switch and jaws tripping speed. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test drive machine with 125% of rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car safeties at rated speed with rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test unintended car movement with 125% of rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test elevator on emergency power. Re-inspection required 10/19/2023