MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean debris form elevator pit
|
10/19/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Car Tops
|
|
|
Clean dirt from elevator car top
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test elevator on emergency power. Re-inspection required
|
11/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work on emergency power or normal power. Repair or replace
|
10/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Check governor rope pull through and pull out force. Re-inspection required
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Check governor switch and jaws tripping speed. Re-inspection required
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test drive machine brake with 125% of rated load. Re-inspection required
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car safeties at rated speed with rated load. Re-inspection required
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test unintended car movement with 125% of rated load. Re-inspection required
|
10/19/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test elevator on emergency power. Re-inspection required
|
10/19/2023
|