Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Yes No Seal all penetrations in the hoistway. 4/27/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes No Complete installation and testing of components of fire service. 4/27/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 8.11.2.1.2(o) Yes No Repair manual rescue brake release. 3/19/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Check govenor rope pull through and pull out force. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Check governor switch and jaws tripping speed. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test drive machine brake with 125% of rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test car safeties at rated speed with rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test unintended car movement with 125% of rated load. Re-inspection required 10/19/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Clean debris from elevator pit. 10/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops No No Clean dirt from elevator car top 10/19/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-Communication inoperable and shall be repaired, or replaced. Reinspection required. 12/20/2024