Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.6 - Governor-rope tension devices 8.11.2.1.5(g) The tail sheave switch shall be wired per the manufactures’ specifications. 1/23/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release Means to manually release machine brake (UPS Unit) shall be operational. 1/23/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on site documentation required by A17.1-2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Only schematics are present. 12/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP, including PM records and monthly fire service test log, not being properly documented. 11/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Standby power shall be tested and operate in conformance of code. 1/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x 8.4.10.1.2(C) - Counterweight derailment does not work. 11/16/2020