Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x The emergency/standby power shall be tested. Note: Building personnel were not prepared to perform this test. 12/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x The elevator had to be red tagged during the annual inspection and category 5 test. The annual inspection and category 5 test shall be completed. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.16.8 x x The car would not hold 125% of rated loaded at the bottom landing. Elevator Red Tagged. 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The current extinguisher is a BC type. 12/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.14 - Hoistway clearances 8.11.2.1.3(t) 2.11.10.1 - Provide hoistway door sill guard at 5th floor. 9/8/2020