ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.14 - Hoistway clearances
|
8.11.2.1.3(t)
|
|
|
2.11.10.1 - Provide hoistway door sill guard at 5th floor.
|
9/8/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.16.8
|
x
|
x
|
The car would not hold 125% of rated loaded at the bottom landing. Elevator Red Tagged.
|
10/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
The elevator had to be red tagged during the annual inspection and category 5 test. The annual inspection and category 5 test shall be completed.
|
10/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
The emergency/standby power shall be tested. Note: Building personnel were not prepared to perform this test.
|
12/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The current extinguisher is a BC type.
|
12/21/2023
|