ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
1/26/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
A category 5 test shall be performed and witnessed in 2022. Note: This unit was scheduled for a category 5 test at the same time as the annual. The category 5 test was delayed due to a different unit at this location being Red Tagged.
|
12/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
The emergency/standby power shall be tested. Note: Building personnel were not prepared to perform this test.
|
12/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The current fire extinguisher is a BC type.
|
12/21/2023
|