Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x The emergency/standby power shall be tested. Note: Building personnel were not prepared to perform this test. 12/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x A category 5 test shall be performed and witnessed in 2022. Note: This unit was scheduled for a category 5 test at the same time as the annual. The category 5 test was delayed due to a different unit at this location being Red Tagged. 12/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 1/26/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The current fire extinguisher is a BC type. 12/21/2023