ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
The front door restrictor shall be operational.
|
7/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
8.6.4.13.1 - The front door restrictor shall be operational. All landing and car-door or gate mechanical and electrical components shall be maintained to ensure safe and proper operation.
|
10/27/2022
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.5 Wedge Rope Sockets
|
|
|
2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced.
|
|
A17.1-2016 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
2.20.9.7.2 Seizing of Rope Ends
|
|
|
2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. 2022 & 2023 documentation missing.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors.
|
11/26/2024
|