Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The Category 5 testing has not been completed on the elevator at this time. The weight test shall be performed, and overspeed valve set before the inspection is completed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 8.11.2.1.1(l) Car hand rail is missing, replace.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Provide feeder location on main line disconnect. NEC 620.51
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Provide feeder location on 110v. disconnect. NEC 620.51
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x This elevator has an overspeed valve device installed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone failed to operate. 4/10/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x Phone failed to operate, does not dial when button is pushed./ Third visit 4/30/2024