ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
1) Emergency operation of signaling devices, lighting, communication and ventilation, shall be maintained. The two-way voice communications shall be available between the car and authorized personnel. This is under maintenance 8.6.4.15 and is not a re-inspect item.
|
2/21/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
8.11.2.1.1(p)
|
|
|
2) Required signs and data plates that are damaged or missing shall be repaired or replaced. Capacity plate is not provided in cab. Ref: 8.11.2.1.1(p)
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
3) Up-to-date wiring diagrams detailing circuits of all electrical protective devices and critical operating circuits shall be available in the machine room. Ref: 8.6.1.6.3
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.14 - Code data plate
|
8.9
|
|
|
4) A data plate that indicates the Code and edition in effect at the time of installation shall be provided. Ref: 8.6.1.5
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.40 - Maintenance Records
|
2.26.1.4 Inspection Operation
|
|
|
5) The Maintenance Control Program shall consist of examinations, maintenance and tests of equipment. No MCP has been put in place. Ref: 8.6.1.2.1
|
11/23/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
6) When the building code requires a sign be posted adjacent to hall call fixtures instructing occupants not to use the elevator in case of fire. This is not a red tag nor a re-inspect item. Ref: 2.27.9
|
2/21/2020
|