Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Gutter water pipes that run over controller 3/23/2021
conversion conversion n/a Escape hatch needs to be bolted down from car top 3/23/2021
conversion conversion n/a Pit needs permanent light fixture switch shall be accesible from pit access door 3/23/2021
conversion conversion n/a Cover needed for interlock at Floor L 3/23/2021
conversion conversion n/a Pit needs ladder, it shall extend 30in above the sill or provided hand grip 3/23/2021
conversion conversion n/a Floor B and Floor 1 needs about 1 1/2 in spacer on hoistway door to meet allowable space requirements 3/23/2021
conversion conversion n/a Pit full of oil needs to be removed 3/23/2021
conversion conversion n/a Pit stop switch shall provided IAW A17.1 1995 It shall be accessible from pit access door 3/23/2021
conversion conversion n/a Need 5 Gal pit bucket in pit to collect oil from overflow from head 3/23/2021
conversion conversion n/a If hydraulic cylinder not replaced the packing for cylinder head needs to be replaced. 3/23/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No guard on car light fixture
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door not self closing or locking
MO Minimum : Elevators (H) - Machine Rooms (H)2 Gutter / shield pipes in machine room to protect controller
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No pit light
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 To much space between inside hoist way door and car gate
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No "maintenance control program" records