ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. The rescue plan is missing. (This item is for notification purposes for future violation in 2022)
|
7/27/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
Emergency/standby power operation of the elevator shall be operational.
|
7/27/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.6 - Governor-rope tension devices
|
2.18.7
|
x
|
|
Subsequent to the first stop of the car following the opening of the tail sheave tension switch, the car shall remain inoperative until the switch is manually reset. Note: Currently this switch opens the safety circuit, stopping the car immediately.
|
8/31/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power operation of the elevator must be tested annually.
|
11/8/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors.
|
8/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service testing must be documented monthly.
|
8/27/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Hoist rope tail retaining clips shall be properly spaced.
|
8/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit shall be kept clean. Remove excess debris and rail oil puddles.
|
8/27/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
|
|
Replace missing "HAS" board electrical box cover, exposed wiring.
|
8/27/2024
|