Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.1 - Door Re-opening device 8.6.4.13.1(c) Door Reopening Devices The mechanical car gate reopening device was not working on the day of inspection. Repair the reopening device for passenger safety. 9/4/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting A light fixture inside the elevator is not operational and shall be repaired. 9/4/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) Car Lighting A car light fixture in the car is not operational and shall be repaired to provide adequate lighting inside the elevator car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1 Illumination and Outlets Required A car light fixture in the car is not operational and shall be repaired to provide adequate lighting inside the elevator car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.